Message Meaning LED response
SF-LED on central
unit
Input LEDs on central unit or ex‐
pansion module
Cross-circuit at input x A cross-circuit was detected at input x. Red The IN LEDs of the sensor are ash‐
ing green.
Start signal duration in‐
valid
Only with start type "Monitored start":
The start signal time monitoring ele‐
ment detected a violation.
‑ ‑
Start condition not full‐
led
is set if:
• A sensor test was not executed in
the case of an active startup test
function
• A discrepancy condition violation
is present
• The value "1" is not present simul‐
taneously at all available (parame‐
terized) function inputs (IN1, ...)
• A signal sequence violation is
present
• A cross-circuit is present in the
case of cross-circuit monitoring
‑ ‑
7.3.3.5 Protective door with lock
The table below lists all the messages and corresponding LED responses to the "Protective Door
with Lock" function element.
Message Meaning LED response
SF-LED on cen‐
tral unit
Input LEDs on central unit or
expansion module
Startup test required This message is set in a parameterized
startup test on each restart and each time
the substitute value is changed to a real
value until the connected sensor is actu‐
ated at least once.
‑ The IN LEDs of the sensor are
ashing green.
Sequence condition not full‐
led
The sequence condition was not fullled in
accordance with the parameter assign‐
ment.
ashes red The sensor that triggered the
sequence violation is ashing.
Discrepancy condition violated is set if:
• After the discrepancy time has
elapsed, the signal states at the inputs
monitored are dierent
• The signal states of the inputs moni‐
tored had not all previously been reset
simultaneously to the value "0" when
they are set to "1"
ashes red The IN LEDs of the sensor are
ashing green.
Diagnostics / service
7.3 Diagnostics with LEDs
SIRIUS 3RK3 Modular Safety System
274 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006