8.11 EM 4/8F-RO
Technical data of the expansion module 4/8F-RO
Device data
Number of outputs 8 safety-related single-channel relay outputs
Height
• Screw terminals
• Spring-loaded terminals
102 mm
105 mm
Width 45 mm
Depth 124 mm
Weight 400 g
Electrical data
Supply voltage/
rated control supply voltage Us
24 V DC
Operating range 0.85 to 1.15 x Us
Rated insulation voltage U
i
300 V
Rated impulse withstand voltage U
imp
2.5 kV
1)
Total power consumption 140 mA
Rated power at Us 3.0 W
Utilization category in accordance with EN 60947‑5‑1
(relay outputs)
• AC 15 at 230 V
• DC 13 at 24 V
2 A
1 A
Resetting time
2)
of the safety-related outputs t
RT
420 ms
Mechanical durability 10 x 10
6
switching cycles
Max. switching frequency z at rated operational current 360 1/h
Conventional thermal current I
th
3 A
Output contacts protected with fuses NH type 3NA, DI‐
AZED type 5SB, NEOZED type 5SE
• Operating class gL/gG
• Operating class quick response
4 A
6 A
Safety data according to EN ISO 13849-1
Probability of a dangerous failure per hour (PFH
d
) 7.15 x 10
-9
1/h
Probability of a dangerous failure on demand (PFD) 4.36 x 10
-5
1)
Protective separation, reinforced insulation 4 kV between input circuit and output contact current paths.
2)
Time from instant an output is switched o to the instant the output reaches a state that permits it to be switched on again.
Technical data
8.11 EM 4/8F-RO
SIRIUS 3RK3 Modular Safety System
380 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006