6.6 Integration into PROFINET master systems
6.6.1 Setting the PROFINET communication parameters
6.6.1.1 Options
PROFINET communication parameters
The requirement for communication via PROFINET is the setting of the PROFINET
communication parameters in the IO device (= safety relay with 3SK25 PROFINET interface). The
PROFINET communication parameters consist of the device name and the IP parameters.
Setting option of the PROFINET communication parameters
The following options are available for the safety relay for setting and changing the
communication parameters:
Setting in SIRIUS Safety ES during the con󹪝guration
Setting via PROFINET services, e.g. in STEP 7 or in SIRIUS Safety ES.
1
3
2
4
352),1(7
PC/PG with SIRIUS Safety ES via device interface on the PROFINET interface
PC/PG with Ethernet interface and STEP 7 or SIRIUS Safety ES via 󹪝eldbus interface on the PROFINET
interface
3SK25 PROFINET interface
3SK2 / 3RK3 safety relay
The device name is required, at a minimum, for the transfer of the device parameters via
PROFINET . It is always possible to transfer the device parameters via the device interface X1
, even if no device name has been set.
The PROFINET communication parameters can in principle be changed via both paths. The
communication parameters that were last written to the 3SK25 PROFINET interface / safety relay
are valid.
In SIRIUS Safety ES, the access paths via PROFINET services can be blocked in the "Properties
interface module" in "Con󹪝guration".
Operation
6.6 Integration into PROFINET master systems
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006 235