7.3.3.8 Two-hand operation
The table below lists all the messages and corresponding LED responses to the "two-hand
operation" function element.
Message Meaning LED response
SF-LED on central unit Input LEDs on central unit
or expansion module
Discrepancy condition
violated
is set if:
• After the discrepancy time has
elapsed, the signal states at the
inputs monitored are dierent
within one or between to two
pushbuttons.
• The signal states of the inputs
monitored had not all previously
been reset simultaneously to the
value "0" when they are set to "1"
ashes red The IN LEDs of the sensor are
ashing green.
Cross-circuit at input x A cross-circuit was detected at input x. red The IN LEDs of the sensor are
ashing green.
Start condition not full‐
led
is set if:
• If both pushbuttons were not
pressed "synchronously," that is,
they were pressed with a time o‐
set greater than 0.5 s
• A discrepancy condition violation
is present
• The value "1" is not present simul‐
taneously at IN1 ... 2 / 4
• A cross-circuit is present
‑ ‑
Pushbutton stuck
(not in the case of 3RK3
Basic)
The pushbutton is stuck. ashes red The IN LEDs of the sensor are
ashing green.
Do not release both push‐
buttons simultaneously
(not in the case of 3RK3
Basic)
The two pushbuttons were not re‐
leased simultaneously.
ashes red The IN LEDs of the sensor are
ashing green.
Diagnostics / service
7.3 Diagnostics with LEDs
SIRIUS 3RK3 Modular Safety System
278 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006