Figure 6-7 Signal ow of example 1
The reaction times are calculated as follows:
W
6
$6,
6
0665.
W
$
$6,
$
[W
&<&/DVL
$6,
,1
$6,
4
[W
&<&/DVL
W
56$B
W
)56$B
W
5/
W
)5/
Figure 6-8 Reaction times MSS 3RK3 Advanced - example 1
Reaction time "sensor - actuator"
(in error-free operation)
t
RSA_1
= t
S
+ (2 x t
CYCLasi
)
+ t
RL
+ (2 x t
CYCLasi
) + t
A
= t
S
+ (4 x t
CYCLasi
)
+ t
RL
+ t
A
Fault reaction time "sensor - actuator";
for AS-i output signal identical to t
RSA_1
t
FRSA_1
= t
RSA_1
t
RL
= t
FRL
Formula Description
t
RSA_1
Reaction time "sensor - actuator" in error-free operation
t
FRSA_1
Fault reaction time "sensor - actuator"; for AS-i output signal identical to t
RSA_1
t
S
For the reaction time of the AS‑i sensor (ASI S), see the documentation of the sensor.
t
CYCLasi
AS-i cycle time, max. 5 ms
• Transmission duration from signal acquisition on the safety-related AS-i input slave
(ASI IN) to the logic of the MSS 3RK3
• Transmission duration from the logic of the MSS 3RK3 to the input terminal on the safety-
related AS-i output (ASI Q)
t
RL
Reaction time of the logic of the MSS 3RK3 in error-free operation
Operation
6.1 Response times
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006 179