• Group warning (for MSS 3RK3 Basic only)
(e.g., wait for startup test)
Display on the central unit Remedy
LED Display
DEVICE Depending on the operat‐
ing state
Acknowledgment is not necessary. When the logic is cor‐
rect, the warning is automatically canceled.
SF -
The warning is signaled when the LEDs
of the corresponding inputs start ash‐
ing.
• Group prewarning (not in the case of MSS 3RK3 Basic)
(e.g., wait for startup test)
Display on the central unit Remedy
LED Display
DEVICE Depending on the operat‐
ing state
Acknowledgment is not necessary. When the logic is cor‐
rect, the warning is automatically canceled.
SF -
The warning is signaled when the LEDs
of the corresponding inputs start ash‐
ing.
(e.g., safety sensor triggered)
Display on the central unit Remedy
LED Display
DEVICE Depending on the operat‐
ing state
Acknowledgment is not necessary. When the logic is cor‐
rect, the warning is automatically canceled.
SF -
The LEDs of the relevant inputs do not
light up.
Parameterization or conguration error
This category of error only occurs in conguring mode. This error is caused if the conguration
is either not available or is incorrect, for example.
Display on the central unit Remedy
LED Display
DEVICE Yellow Acknowledgment is not necessary. When the parameteriza‐
tion is correct, the error is automatically canceled.
SF red
Diagnostics / service
7.2 Diagnostics concept
SIRIUS 3RK3 Modular Safety System