NOTICE
Material damage caused by electrostatic charge
When handling and installing the MSS components, ensure that the components are protected
from being electrostatically charged. Changes to the system con󹪝guration and wiring are only
permissible while the supply voltage is switched o󹪜.
Connection of MSS 3RK3 central units is only permissible when the power supply is switched
o󹪜.
Note
Operational faults and malfunctions in communication
If the EMC Directive 2014/30/EU is not complied with when systems and devices are installed,
communication breaks may occur.
Note
Simultaneity of signals
Depending on when a signal change takes place within the cycle, the signal change is detected
either in the same cycle or not until the following cycle time.
This means it is possible for supposedly simultaneous signal changes to be detected at two
di󹪜erent inputs by the logic, but not simultaneously.
Take this behavior into account when creating your con󹪝guration.
Note
Do not cover all unused device and system interfaces.
Product-speci󹪝c information
2.1 General safety notes
SIRIUS 3RK3 Modular Safety System
26 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006