LED Display Description
SF O No group error
red Group fault
1)
that requires acknowledgment
(wiring, communication, parameterization or conguration error)
red ashing
0.5 Hz (ratio 1:1)
Self-acknowledging group fault (logic error)
(e.g. discrepancy time violation, violation of a signal sequence)
F-IN1, F-
IN2
O Input signal not present
green Input signal present
green ashing
(1.75 s ON/
0.25 s OFF)
Error detected (cross-circuit at input / wirebreak / short-circuit to power
cable / discrepancy error / feedback circuit error / sequence error / error
during startup test)
Input signal present
green ashing
(0.75 s ON/
1.25 s OFF)
Error detected (cross-circuit at input / wirebreak / short-circuit to power
cable / discrepancy error / feedback circuit error / sequence error / error
during startup test)
Input signal not present
IN3, IN4,
IN5, IN6,
IN7, IN8
O Input signal not present
green Input signal present
green ashing
(1.75 s ON/
0.25 s OFF)
Error detected (feedback circuit error/sequence error)
Input signal present
green ashing
(0.75 s ON/
1.25 s OFF)
Error detected (feedback circuit error/sequence error)
Input signal not present
Q1, Q2 O Output signal not present
green Output signal present
1)
Please note the safety information below.
WARNING
System Restart After Fault Acknowledgment/Restart
Can Cause Death, Serious Injury, or Damage to Property.
After fault acknowledgment/restart, the system immediately resumes operation with the
values specied by the control, and outputs are activated if the power-on condition is fullled.
Take appropriate measures (e.g. start button with monitored starting) to prevent unintentional
restarting and to ensure a dened start of the system.
Reference
You will nd further information on the LED display during startup in Chapter "Startup / self-test
of the MSS 3RK3 Advanced (Page 85)"
Diagnostics / service
7.3 Diagnostics with LEDs
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006 261