1 safety-related two-channel semiconductor output
2 test outputs for sensor supply and monitoring when used with safety-related sensor inputs
Note
Safety-related outputs
If you use the safety-related outputs with a two-channel shutdown, a fault exclusion, such as a
short-circuit to P or M, is required. This condition is met within a control cabinet and when the
connection cables are installed in such a way that they are protected.
MSS 3RK3 ASIsafe basic on the AS-i bus
The MSS 3RK3 ASIsafe basic can perform various functions on the AS‑i bus:
Simulation of up to 4 non-safety-related AS-i slaves
Simulation of up to 8 safety-related AS-i input slaves
Simulation of up to 8 safety-related AS-i output slaves
Display of up to 31 safety-related AS-i outputs
Monitoring of up to 14 non-safety-related AS-i slaves
Monitoring of up to 31 safety-related AS-i input slaves
You will 󹪝nd further information in Chapter "Connecting to the AS-i master via AS-Interface
(Page 202)."
Structure of the 3RK3 ASIsafe basic central unit
Front view No. Meaning
7),1,1,1,1$6L
7),1,1,1,1$6L
444/0)(
;;
'(9,&(
6)
5(6(7
),1
066$6,VDIH
$6L
7($&+
24V
DC
,1,1,14
),1,1,1,14

3RK3121-1AC00
Removable terminal block D
Removable terminal block C
RESET button
Removable terminal block A
External memory module (X3; sealable)
Label
Display LEDs
Connection of PC or programming device,
interface module, diagnostics display (X1)
Description of the hardware
5.1 Description of the individual modules
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006 87