SIMPLEX 4100 EWIS Page 3
INSTALLATION MANUAL
Document No.: 4100-M011 March 1998 Issue 1.0
2. INSTALLATION PROCEDURE
2.1 CABINET INSTALLATION
The 4100 EWIS system cabinet should be mounted such that all indicators and
controls are not less than 750 mm and not more than 1850 mm from the floor level.
2.1.1 Surface Mount
For surface mount, 4 bolts secure the Back Box cabinet or screws through predrilled
12 mm holes on the rear of the cabinet.
2.1.2 Recess Mount
For a recess mounting of the Back Box cabinet allow a cut out equal to the size of
the cabinet plus 10mm all round clearance.
2.2 CARD INSTALLATION
The following instructions provide a systematic method for installing system printed
circuit boards (or cards) in a 4100 EWIS system if these are not already installed.
STEP # ACTION
U 1.
Open each system card box and remove the system cards from the
container.
U 2.
Install the master control card.
U 3.
Install the RS-232/2120 Communications Card or the RS-485 Network
Interface Card.
U 4.
Install the daughter cards.
U 5.
Verify all cabling and wiring harness connections. Refer to Simplex field
wiring Diagram (Part No. 841-731).
U 6.
Verify all system wiring is terminated at specified terminal locations as
specified by Simplex Field Wiring Diagram (Part No. 841-731)
U 7.
Perform a complete system test of all installed devices.
U 8.
Install and secure the retainer panel on the back box.
U 9.
Mount the door on the back box.