SIMPLEX 4100 EWIS  Page 25
INSTALLATION MANUAL
Document No.: 4100-M011 March 1998  Issue 1.0
PLUGGABLE RESISTOR SETTINGS
DRIVE # RESISTOR # INPUT OUTPUT
1 20 2K  .5W 20 OHM  1W
2 21 2K  .5W 20 OHM  1W
3 22 2K  .5W 20 OHM  1W
4 23 2K  .5W 20 OHM  1W
5 24 2K  .5W 20 OHM  1W
6 25 2K  .5W 20 OHM  1W
7 26 2K  .5W 20 OHM  1W
8 27 2K  .5W 20 OHM  1W
9 28 2K  .5W 20 OHM  1W
10 29 2K  .5W 20 OHM  1W
11 30 2K  .5W 20 OHM  1W
12 31 2K  .5W 20 OHM  1W
13 32 2K  .5W 20 OHM  1W
14 33 2K  .5W 20 OHM  1W
15 34 2K  .5W 20 OHM  1W
16 35 2K  .5W 20 OHM  1W
17 36 2K  .5W 20 OHM  1W
18 37 2K  .5W 20 OHM  1W
19 38 2K  .5W 20 OHM  1W
20 39 2K  .5W 20 OHM  1W
21 40 2K  .5W 20 OHM  1W
22 41 2K  .5W 20 OHM  1W
23 42 2K  .5W 20 OHM  1W
24 43 2K  .5W 20 OHM  1W
For Input Contact Monitors For Relays LED/Lamps
Table 4 24 Point Graphic I/O Card Pluggable Resistors
NOTE: Systems are shipped from the factory with 3.3K OHM resistors.  Use 3.3K
OHM resistors for contact monitors and 20 OHM resistors for RELAY or
LED/lamp outputs.