SIMPLEX 4100 EWIS Page 35
INSTALLATION MANUAL
Document No.: 4100-M011 March 1998 Issue 1.0
The Fire Indicator Panel Trip can be terminated in the 4100-5002-monitor card.
There are 8 Input zones per card and are labelled ZN1 to ZN8 (See
Figure 14).
Each input zone monitors a set of Normally Open Contacts located in the Fire
Indicator Panel and is terminated with a 3K3 End Of Line Resistor.