6.
ForcreatinganRS485bus-connectallB,AandGpinsinallinverters.Thefollowingfigureshowsthis
connectionschema:
Figure 38: Connecting the inverters in a chain
NOTE
Do not cross-connect B, A and G wires. Do not insert wires into RS485- 2 pins.
7. Tightentheterminalblockscrews.
8. Checkthatthewiresarefullyinsertedandcannotbepulledouteasily.
9.
PushtheRS485terminalblockfirmlyallthewayintotheconnectorontherightsideofthe
communicationboard.
10.
TerminatethefirstandlastSolarEdgedevice(inverter/Controlandcommunicationgateway,etc.)in
thechainbyswitchingaterminationDIP-switchinsidetheinvertertoON(movetheswitchup).The
switchislocatedonthecommunicationboardandismarkedSW7.
Figure 39: RS485 termination switch
NOTE
Only the first and last SolarEdge devices in the chain should be terminated. The other inverters
in the chain should have the termination switch OFF (down position).
Chapter 10: Setting Up Communication to the Monitoring Portal
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.0
77

Table of Contents

Other manuals for SolarEdge StorEdge SE7600A-USS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SolarEdge StorEdge SE7600A-USS and is the answer not in the manual?

SolarEdge StorEdge SE7600A-USS Specifications

General IconGeneral
BrandSolarEdge
ModelStorEdge SE7600A-USS
CategoryInverter
LanguageEnglish

Related product manuals