Measurement of resistance-to-earth R
E
(for TT)
Selected
nominal cur-
rent
of RCD
Measurement of touch voltage U
B
in relation to nominal differential current
Test range according to IEC 61557-6: 10.0 V...99.9 V
Measurement of RCD disconnection current I
A
for sinusoidal differential current
Test range according to IEC 61557-6: (0.3...1.0)I
Δn
Selected nomi-
nal current
of
RCD
it is possible to start the measurement from the positive of the negative half of forced leakage cur-
rent
test current duration............................... max. 8.8 s
Measurement of RCD disconnection current I
A
for differential unidirectional pulsed current and
unidirectional
pulsed current with 6mA direct current offset
Test range according to IEC 61557-6: (0.35...1.4)I
n
for I
n
≥30 mA and (0.35...2)I
n
for I
n
=10 mA
Selected nomi-
nal current
of
RCD
measurement may be performed for positive or negative half-periods of forced leakage current
test current duration................................ max. 8.8 s