10.1.8 Measurement of insulation resistance
Measurement range, according to IEC 61557-2 for U
N
= 50 V: 50 kΩ…250 MΩ
Display range for
U
N
= 50 V
(3% m.v. + 8 digits),
[(5% m.v. + 8 digits)] *
* – for WS-03 and WS-04 leads
Test range according to IEC 61557-2 for U
N
= 100 V: 100 kΩ…500 MΩ
Display range for
U
N
= 100 V
(3% m.v. + 8 digits)
[(5% m.v. + 8 digits)] *
* – for WS-03 and WS-04 leads
Test range according to IEC 61557-2 for U
N
= 250 V: 250 kΩ…999 MΩ
Display range for
U
N
= 250 V
(3% m.v. + 8 digits)
[(5% m.v. + 8 digits)] *
* – for WS-03 and WS-04 leads
Test range according to IEC 61557-2 dla U
N
= 500 V: 500 kΩ…2.00 GΩ
Display range for
U
N
= 500 V
(3% m.v. + 8 digits)
[(5% m.v. + 8 digits)] *
(4% m.v. + 6 digits)
[(6% m.v. + 6 digits)] *
* – for WS-03 and WS-04 leads
Test range according to IEC 61557-2 for U
N
= 1000 V: 1000 kΩ…4,99 G
Display range for
U
N
= 1000 V
Test voltage: 50 V, 100 V, 250 V, 500 V i 1000 V
Accuracy of generated voltage (Robc [] 1000*U
N
[V]): -0% +10% from the set value
Detection of a dangerous voltage before commencing a measurement