MPI-540 USER MANUAL
93
3.8.4 Measurements using AutoISO-1000c
WARNING
During measurements of insulation resistance, dangerous voltage up to 1 kV
occurs at the ends of test leads of the meter.
It is forbidden to disconnect test leads before the measurement is completed.
Failure to obey the above instruction will lead to electric shock with high volt-
age and make it impossible to discharge the tested object.
Select item R
ISO
, to call up the
measurement screen.
Connect AutoISO-1000c adapter.
The meter detects this fact auto-
matically and changes the ap-
pearance of the screen.
Enter the measurement settings in accordance with section 3.8.1.