Prospective fault current calculated and displayed by the meter may slightly differ from the val-
ue calculated by the user with a calculator, basing on the displayed value of the impedance,
because the meter calculates the current from unrounded value of fault loop impedance (which
is used for displaying). As the correct value, consider I
k
current value, displayed by the meter or
by firmware.
10.1.5 Measurement of parameters of RCD
Measurement of RCDs type: AC, A, B, D, F
Rated operating voltage U
n
: 110 V, 115 V, 127 V, 220 V, 230 V, 240 V
Operating voltage range: 95 V…270 V
Rated mains frequency f
n
: 50 Hz, 60 Hz
Operating frequency range: 45…65 Hz
RCD trigger and response time test t
A
(for measurement function t
A
)
Test range according to IEC 61557-6: 0ms ... to the upper limit of displayed value
1)
for I
n
= 10 mA and 0.5 I
n
uncertainty is ±(2% m.v. + 3 digits)
Accuracy of differential current setting:
for 1*I
n
, 2*I
n
i 5*I
n
..................................................................... 0..8%
for 0.5*I
n
.................................................................................... -8..0%
Effective value of forced leakage current at measurement of RCD [mA] disconnection time