EasyManua.ls Logo

Sonel MPI-540 - Measurement of Current (True RMS); Frequency Measurement

Sonel MPI-540
208 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MPI-540 USER MANUAL
181
10.2.4 Measurement of current (True RMS)
Current
Range and condi-
tions
Resolution
Basic uncertainty
I
RMS
(AC+DC)
Basic uncertainty of the device
10% I
nom
≤ I
RMS
<
100% I
nom
0.01% I
nom
2%
Flexible clamps F-1A/F-2A/F-3A
0..3000 A
(10 kA
p-p
@ 50Hz)
0.01% I
nom
Additional uncertainty
1% (2% taking into account additional
error due to the position)
Hard clamps C-4A
0..1000 A
(3600 A
p-p
)
0.01% I
nom
Additional uncertainty
0.1..10 A: (3% + 0.1 A)
10 A: 3%
50 A: 1.5%
200 A: 0.75%
1000..1200 A: 0.5%
Hard clamps C-5A
0..1000 A
(3600 A
p-p
)
0.01% I
nom
Additional uncertainty
0.5..100 A: ≤ (1.5% + 1 A)
100..800 A: ≤ 2.5%
800..1000 A AC: ≤ 4%
800..1400 A DC: ≤ 4%
Hard clamps C-6A
0..10 A
(36 A
p-p
)
0.01% I
nom
Additional uncertainty
0.01..0.1 A:  (3% + 1 mA)
0.1..1 A: 2.5%
1..12 A: 1%
Hard clamps C-7A
0..100 A
(360 A
p-p
)
0.01% I
nom
Additional uncertainty
0..100 A:  (0,5% + 0,02 A) (45..65 Hz)
0..100 A:  (1,0% + 0,04 A)
(40..1000 Hz)
Crest Factor
1..10 (max. 3.6 for
I
nom
)
for I
RMS
≥ 1% I
nom
0.01
5%
10.2.5 Frequency measurement
Frequency
Range and conditions
Resolution
Basic
uncertainty
f
40..70 Hz
15% U
nom
≤ U
RMS
≤ 120% U
nom
0.01 Hz
0,05 Hz

Table of Contents

Other manuals for Sonel MPI-540

Related product manuals