MPI-540 USER MANUAL
94
The meter is ready for measure-
ment.
Live mode
U interference voltage
Description of function icons
scrolling down the list of
measurements
scrolling up the list of meas-
urements
Connect AutoISO-1000c adapter
to the lead tested.
Press START to start measure-
ment.
During the measurement the
H.V./REC/CONT. diode is lit in
orange.
If any of the voltages exceeds al-
lowable voltage value (50 V),
Object under voltage message
is displayed and the measure-
ment is blocked.
First, checking of voltages on par-
ticular pairs of wires is performed.
If any of the voltages exceeds al-
lowable voltage, the symbol of
this voltage is displayed (e.g.
VOLTAGE! L1PE), and the
measurement is interrupted.