R – resistance of the tested circuit
X
L
– reactance of the tested circuit
U
L-N
– voltage relative to the neutral
conductor
f – frequency
Selecting the bar hides the
menu.
Save the measurement to the meter memory using the icon. A detailed description of
memory management is contained in section 5.1.3.
The last measurement can be recalled using the icon.
When many measurements are performed in short time intervals, the meter may
emit a large amount of heat. As a result of this, the housing of the device may be-
come hot. This is normal. In addition, the meter is equipped with the protection
against excessive temperature.
After approx. 15 consecutive measurements of the fault loop wait until the instru-
ment cools down. This limitation is due to the high current measurement and multi-
functionality of the meter.
Minimum interval between successive measurements is 5 seconds. The displayed
message indicates that it is possible to perform another measurement.
Until the message is displayed, the meter prevents any measurements.