Instruction Manual
for
AS380 Series Elevator Integrated Drive Controller
166
F123——call controller mode setting, this parameter is used to set the call mode of the call
controller and to define the address of call controller.
0: for the standard 04 program board, only call fro front door. The address 148
correspond to the floor 148 front door call.
For the customized 04 program board for 64 floors, front door call, rear door call, and
the disabled call all can be provided. The address of 164 correspond to the front
door call of the floors 164. The address of 65128 correspond to that of rear door
call, 129192 correspond to the disabled call.
1: only for standard 04 program board, front door call and rear door call
are provided. The address of 148 correspond to the front door call of the floor 1
48.
2: only for standard 04 program board, front door call and the disabled call are provided.
The address of 148 corresponded to the front door call of the floor 148, 4996
corresponded to the disabled door call of floor 148
3: only for standard 04 program board, the highest floor is 32nd. Front door call, rear
door call, the disabled call are provided. The address of 132 corresponded to the
front door call of the floor 132. 3364 corresponded to the rear door call of the
floor 132, 6596 corresponded to the disabled call of the floor 132.
F124——the function definition of X16 input point of main board
0: Input point of emergency leveling function under the circumstance of blackout.
1: action input point of earthquake device
2: input point for emergency power supply condition of the building emergency
power supply operation function.
F128—— control mode for front/ rear door. 0: the separate control of front door
and rear door. 1: integrated control of front door and rear door.
F129—— activate the pre-opening of door and re-leveling of door opening.
The range set from 0 to 3. 0: all deactivated. 1: only activate the pre-opening of door.
2: only activate the function of re-leveling of door-opening. 3 activated both two
functions mentioned above.
F130—— holding door-opening/closing torque. 0: no torque holding. 1: door-opening torque
holding, 2: door-closing torque holding, 3: door-opening/closing torque. 4: only
the door-closing torque holding during operation.
F131F133 ——F131-F133 Time section floor blockade floor set related parameter. F131 is
the floor setting, F132 is the beginning time setting, F133 is the closure time setting. Related
parameter F161 is the turn-on time section floor function parameter.
The following is establishes the demonstration:
When F131 = 1, establishes F132 = 1000, F133 is 1200, then 1 building's blocking time is
10:00-12:00
When F131 = 1, establishes F132 = 2300, F133 is 800, then 1 building blocking time for
evening 23:00 to second day of early morning 8:00
Adjusts F131 value and corresponding F132 and F133 may establish 64 floor time section
blocking time, does not block the floor does not establish F132 and F133 then
F132 and the F133 time establishment's range of validity is 0-2359 expressing 0:00:23:59.
F137F139,F199—non service floor setting of switch control. F137 set the value from the