11 | Commissioning STOBER
166
02/2019 | ID 442728.05
2. Direct connection tab > IP address column:
Mark the drive controller in question or activate all those listed using the context menu.
Confirm your selection with OK.
ð The Assignment window opens. All drive controllers connected to the selected network
interface are displayed.
3. Select the first drive controller to which you would like to transfer the test configuration.
Open the corresponding Do not establish connection drop-down menu and select Send.
4. Open the Create new drive controller drop-down menu and select the drive controller to
which you would like to transfer the test configuration.
5. Repeat steps 3 and 4 for all other drive controllers to which you wish to transfer your test
configuration.
6. Click on Establish online connections.
ð The test configuration is transferred to the selected drive controllers.
Saving the test configuration
1. Highlight the drive controller you have transferred the test configuration to in the project tree
and click on the first projected axis in the project menu > Wizard section.
2. Select the Save values wizard > Action management section and click on Save values.
3. As the configuration is only effective after a restart of the drive controller, select the Restart
wizard > Action management section and click on Restart.
Activating the control panel and testing the project configuration
ü
The STO safety function must not be activated.
1. Select Jog control panel.
2. Click Control panel on and then on Enable.
ð The drive is controlled using the activated control panel.
3. Move the axis step-by-step and test the direction of motion, velocity, distance, etc. using
the Jog+, Jog−, JogStep+ and JogStep− buttons.
4. Optimize your project configuration based on your test results as necessary.
5. To deactivate the control panel, click on Control panel off.
Information
Jog+ and Jog− cause a continual manual movement in the positive or negative direction. If both
buttons are active, no movement is executed.
JogStep+ and JogStep− move the drive relative to the current actual value by the step width
specified in I14.
Jog+ and Jog− have a higher priority than JogStep+ and JogStep−.