6 | Technical data STOBER
38
02/2019 | ID 442728.05
6 Technical data
Technical data for the drive controllers, supply modules and accessories can be found in the
following chapters.
6.1 General technical data
The following specifications apply equally to the SI6 drive controller and the PS6 supply module.
Device features
Protection class of the device IP20
Protection class of the installation
space
At least IP54
Radio interference suppression Integrated line filter in accordance with EN 61800-3:2012,
interference emission class C3
Overvoltage category III in accordance with EN 61800-5-1:2008
Test symbols
Tab. 11: Device features
Transport and storage conditions
Storage/
transport temperature
−20°C to +70°C
Maximum change: 20K/h
Relative humidity Maximum relative humidity 85%, non-condensing
Vibration (transport) in accordance
with DIN EN60068-2-6
5Hz ≤ f ≤ 9Hz: 3.5mm
9Hz ≤ f ≤ 200Hz: 10m/s²
200Hz ≤ f ≤ 500Hz: 15m/s²
Tab. 12: Transport and storage conditions
Operating conditions
Surrounding temperature during
operation
0°C to 45°C with nominal data
45°C to 55°C with derating −2.5%/K
Relative humidity Maximum relative humidity 85%, non-condensing
Installation altitude 0m to 1000m above sea level without restrictions
1000m to 2000m above sea level with −1.5%/100m derating
Pollution degree Pollution degree 2 in accordance with EN 50178
Ventilation Installed fan
Vibration (operation) in accordance
with DIN EN 60068-2-6
5Hz ≤ f ≤ 9Hz: 0.35mm
9Hz ≤ f ≤ 200Hz: 1m/s²
Tab. 13: Operating conditions
Discharge times
Self-discharge of DC link 15min
DC link circuit fast discharge Thanks to PS6 supply module in combination with a braking
resistor:
< 1min
Tab. 14: Discharge times of the DC link circuit