STOBER 7 | Project configuration
02/2019 | ID 442728.05
81
7.4.1 Maximum operation on PS6A24
Drive controller Quick DC-Link Limiting factor Examples
Type Self-
capacitance
C
PU
[mF]
Nominal input
current (DC)
I
1N,PU
[A]
7
Width
[mm]
Type Charging
capacity
(C
max,PU
=
5mF)
Nominal
output current
(I
2N,PU
= 21.4A)
Length of the
copper rails
[max.
1500mm]
Partial load of
50%
Partial load of
25%
SI6A061 0.18 4.2 45 DL6B10 27 devices 5 devices 32 devices 10 devices 20 devices
SI6A062 0.27 8.4 45 DL6B10 18 devices 2 devices 32 devices 5 devices 10 devices
SI6A161 0.47 10.4 65 DL6B11 10 devices 2 devices 22 devices 4 devices 8 devices
SI6A162 0.94 20.7 65 DL6B11 5 devices 1 device 22 devices 2 devices 4 devices
SI6A261 0.94 19.0 65 DL6B11 5 devices 1 device 22 devices 2 devices 4 devices
SI6A262 2.25 41.2 105 DL6B12 2 devices 0 devices 13 devices 1 device 2 devices
SI6A361 2.25 41.2 105 DL6B12 2 devices 0 devices 13 devices 1 device 2 devices
Tab. 76: Maximum operation on one PS6A24 supply module with DL6B20 rear section module