Innagator | Technical Pack178
Fault Description
Dierenttypesoffaultsarebelow:
Fault types Trigger conditions
Charge over-current alarm
Exceeding the parameter set value and set time
(More than 105A, 2s; more than 125A, 5s; more than
140A,2s;lowerthan5°C,setvalue*0.5)
Charge over-current protection
Discharge over-current alarm
Discharge over-current protection
Charge overtemperature alarm
Exceeding the parameter set value and set time
(>45°C,25)
Charge overtemperature protection
Exceeding the parameter set value and set time
(>50°C,2s)
Discharge overtemperature alarm
Exceeding the parameter set value and set time
(>50°C,2s)
Discharge overtemperature protection
Exceeding the parameter set value and set time
(>55°C,2s)
Charge under temperature alarm
Exceeding the parameter set value and set time
(<5°C,2s)
Charge under temperature protection
Exceeding the parameter set value and set time
(<0°C,2s)
Discharge under temperature alarm
Exceeding the parameter set value and set time (<-
10°C,2s)
Discharge under temperature protection
Exceeding the parameter set value and set time (<-
20°C,2s)
Excessivedierentialvoltagealarm
Exceeding the parameter set value and set time
(>500mv, 2s)
Excessivedierentialvoltageprotection
Exceeding the parameter set value and set time
(>800mv, 2s)
Excessivedierentialtemperaturealarm
Exceeding the parameter set value and set time
(>10°C,2s)
Excessivedierentialtemperatureprotection
Exceeding the parameter set value and set time
(>15°C,2s)
Cell overvoltage alarm Tomaintainconsistency,cutothechargingimme-
diately when the full charge calibration rated voltage
of 3.6V is reached. When the voltage drops to 3.35V,
restartitwiththeturnedoredlightindicatorAll
protective red light indicators are always on!
Cell overvoltage protection
Cell undervoltage alarm
Cell undervoltage protection
Pre-charge resistor overtemperature alarm
Exceeding the parameter set value and set time
(>55°C,2s)
Pre-charge resistor overtemperature protection
Exceeding the parameter set value and set time
(>65°C,2s)
Insulation level 1 Exceeding the parameter set value and set time
Insulation level 2 Exceeding the parameter set value and set time
Heatinglmovertemperaturealarm
Exceeding the parameter set value and set time
(>75°C,2s)
Heatinglmovertemperatureprotection
Exceeding the parameter set value and set time
(>80°C,25)