Innagator | Technical Pack29
Technical Parameter of FK-5-1-12
Parameter name Energy storage tank
Protect Area 10 m
2
Height 2.60 m
Volume 26.0 m
3
Design Concentration 5.9%
Ejection Time 10s
Dipping Time 10s
Area of Vent 0.03 m
2
Design Pressure 2.5 Mpa
Ambient Temperature 20°C
Filling Capacity per Bottle 24 kg
Design Dosage of Fire Extinguishing Agent 23.09 kg
Amount of Fire Extinguishing Agent Stored 24 kg
Number of Storage Containers 1
SpecicationsforStorageContainers 30L