Innagator | Technical Pack24
solvents or corrosive chemicals, and abnormal use. If corrosion exceeding RE3 occurs within the guarantee
period, the buyer, TLC, and the paint manufacturer will conduct an inspection to determine the cause.
If it is mutually agreed and accepted that the corrosion is due to defective paint quality and/or poor work-
manship, TLC and/or the paint manufacturer will rectify the issue at their expense.
Decals
Decals applied to the container will be guaranteed by TLC for a period of seven (7) years, ensuring they re-
mainintactwithoutpeelingo,tenting,orexperiencingcolorfading.
1. Design Consideration
"Gasreextinguishingsystem:Physicalcharacteristicsandsystemdesign"IS014520-5;
EN ISO 13943:2000 Fire safety vocabulary;
EN 54-2-2006:Fire detection and alarm systems - Part 2: Control and indicating equipment;
EN 54-4-1998 Fire detection and alarm systems - Part 4: Power supply equipment;
EN 54-7-2000 Fire detection and alarm systems - Part 7: Smoke detectors. Point detectors with scat-
tered, transmitted, or ionized light is used;
EN 54-11-2001 Fire detection and alarm systems - Part 11: Manual alarm buttons;
EN54-23:2010Firedetectionandalarmsystems-Part23:Firealarmequipment-ashalarm;
EN15004-1-2019Fixedreghtingsystems-Gasextinguishingsystems-Part1:Design,installation,and
maintenance;
ISO14520-5Gaseousre-extinguishingsystems-Physicalpropertiesandsystemdesign-Part5:FK-5-1-
12 extinguishant;
EN 50525-1:2011 Electric cables - Low voltage energy cables of rated voltages up to and including
450/750V Part 1: General requirements.
FIRE ALARM
Design Instructions of Automatic System
2. Design Specication
The energy storage container comprises two 20-foot containers equipped with an automatic alarm sys-
tem,gasreextinguishingsystem,andexplosion-proofexhaustsystem.
Design principle: this system has automatic, electric manual two control methods. There are two inde-
pendentdetectionloopsineachreserve.Whentherstresignaloccurs,analarmisissuedtoindicate
thelocationofthereandremindthestatopayattentiontoit.Whentherst2detectorsalsosignal
re,theautomaticreextinguishingcontrollerbeginstodelayphase(0-60sadjustable),afteratime
delay,tocontrolthestartofthecorrespondingreservebottlereinstructions,openthesolenoidvalve
andthenopentheaircylinder,re-ghtingoperationstotherearea,atthesametime,alarmcontrol-
ler receives the feedback signal of the pressure signal, Control panel spray indicator light on; When the
maintenance switch is in the disconnected state, the release signal issued by the alarm controller will not
starttheFK-5-1-12device.Afterthepersonnelondutyconrmtherealarm,themaintenanceswitch
willreachtheconnectedpositionwiththekey,andthenthesystemcanbestarted,andthereextin-
guisher can be sprayed.