EasyManua.ls Logo

SUSS MA6 - N2-Control; Exhaust Flow Control (in Lamp House Intake Tube); Use of Other Lamps; Lamp House 350 W and 350 W Lamp Replacement

SUSS MA6
139 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
M A I N T E NAN C E
OP MA6-8/BA6-8 E Rev05 07-06 Maintenance 45
2
2.4.3. N2-Control
Cooling of lamp sockets is adjusted by two pressure
valves 11/R5.X (X= 2 and 5), one for each lamp
socket (in LH1500). The pressure for the lower sock
-
et is continuously monitored by the pressure meter
11/C4.
The adjustment of the N
2
pressure valves has to
be done following any part exchange in the cool
-
ing system.
Only qualified service personnel is allowed to
perform the adjustment. For details see sections:
Working with the Mask Aligner in Chapter 1 and
Utilities in Chapter 2.
The setting must be completed prior to starting a
lamp. Otherwise there is a risk of lamp explosion.
Caution!
Whenever the ellipsoid mirror or the
coldlight mirror has to be exchanged
be sure to readjust the N2-cooling
nozzle (see fig. below) to cool the lower
lamp socket. Otherwise there is a risk
of lamp explosion.
2.4.4. Exhaust Flow Control
(in Lamp house Intake Tube)
The exhaust flow must be adjusted on site during
machine installation using the factory exhaust sys
-
tem.
The settings must follow the data given in section
Utilites and Lamp Cooling.
After final completion of settings, the flow sensor
(which is optional and is - if installed - located in the
lam house air intake bottom tube) can be checked
and readjusted:
Turn the setting screw in the sensor to the switch-
ing point (indication red/green); then turn back to
green by a half rotation.
2.4.5. Use of Other Lamps
Smaller lamps (550W, 350W) can be used in the
lamp house 1000/1500W if special adapters for the
lamp and for socket cooling are installed.
For required parts and cooling specifications ask
SUSS Service.
2.4.6. Lamp House 350W and
350W Lamp Replacement
The small lamp house differs to the lamp house 100/
1500W in some respect:
It has no access door on the side, it can be
opened only by tilting the head (the upper part) of
the lamp house. The head is secured to the bot
-
tom segment by a screw with access from top
It has no interlock to the lamp power supply. Be-
fore opening the 350W lamp house, the lamp
power supply and the machine must always be
switched OFF! Respect the warning labels at
-
tached to the lamp house!
In standard configuration it does not need ex-
haust for additional cooling or ozone reduction.
Forced N2 socket cooling together with natural
air convection is sufficient to cool the 350W lamp.
The glass bulb of the 350W OSRAM HBO lamp
is especially equipped to minimize deep UV radi
-
ation, resulting in very low ozone generation.
Basic equipment is the 350W lamp.
Potential other lamps are: 200W or 500W. The
200W lamp requires a special lamp socket adapt
-
N
2
-Cooling Nozzle Lamp Socket

Table of Contents

Related product manuals