EasyManua.ls Logo

Synrad FH FLYER - Page 156

Synrad FH FLYER
250 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SYNRAD FH Series Flyer Operator’s Manual Version 3.4
126
Sample input circuits
Flyers optically-isolated inputs are used to start the mark sequence or perform other functions based on
+ 5.0 V
to
+ 24 VDC
NPN Open-Collector
Output Device
FH Flyer Input Section
IN3–7_B
IN3_A
Flyer Input
Circuitry
+ 5.0 V
to
+ 24 VDC
NPN Open Emitter
Output Device
FH Flyer Input Section
IN3–7_B
IN3_A
Flyer Input
Circuitry
signals from external devices. When an external device sinks or sources current through an input, FH Flyer
senses a high-level state (1); when no current ows through the input, Flyer senses a low-level state (0).
FH Flyer inputs are designed for compatibility with standard industrial control circuit voltages in the
range from 5 V to 24 VDC. See Table 6-7 for a listing of possible input signal configurations.
From sinking NPN open collector device
Figure 6-4 illustrates one method of activating a Flyer input from an NPN open collector
logic device that is sinking current.
Input/Output circuitry
Figure 6-4 Activating Flyer input with a current sinking device
For example, to drive Flyer inputs from a PLC using an NPN open collector output module in
a current sinking conguration, connect the voltage source to IN3–7_B (the common re-
turn for inputs IN3_A through IN7_A) and connect each PLC output to Flyer inputs IN3_A
through IN7_A as required. This allows the PLC’s output module to independently activate
Flyer inputs by pulling individual inputs to ground. In Figure 6-4, Flyer input IN3 is
activated when input IN3_A is pulled to ground by the corresponding PLC output. See
Table 6-7 for a listing of possible input signal configurations.

Table of Contents

Related product manuals