142 AI3 SIGNAL FILTER TIME 567 (2.2.41, 2.2.4.2)
When this parameter is given a value greater than 0.0 the function that filters out
disturbances from the incoming analogue signal is activated.
Long filtering time makes the regulation response slower. See parameter ID324.
143 AI3 SIGNAL RANGE 567 (2.2.39, 2.2.4.3)
With this parameter you can select the AI3 signal range.
Table 112: Selection for parameter ID143
Applic.
5 6 7
Sel.
0 0-100% 0-100% 0-100%
1 4 mA/20-100% 4 mA/20-100% 4 mA/20-100%
2 –10…+10V Customised
3 Customised
144 AI3 CUSTOM SETTING MINIMUM 67 (2.2.4.4)
145 AI3 CUSTOM SETTING MAXIMUM 67 (2.2.4.5)
Set the custom minimum and maximum levels for the AI3 signal within - 160...160%.
Example: Min 40%, Max 80% = 8-16 mA.
151 AI3 SIGNAL INVERSION 567 (2.2.40, 2.2.4.6)
Table 113: Selections for parameter ID151
Selection
number
Selection name Description
0 No inversion
1 Signal inverted
152 AI4 SIGNAL SELECTION * 567 (2.2.42, 2.2.5.1)
See ID141.
153 AI4 FILTER TIME 567 (2.2.45, 2.2.5.2)
See ID142.
PARAMETER DESCRIPTIONS VACON · 247