7 PUMP AND FAN CONTROL APPLICATION
7.1 INTRODUCTION
Select the Pump and Fan Control Application in menu M6 on page S6.2.
The Pump and Fan Control Application can be used to control one variable speed drive and
up to four auxiliary drives. The PID controller of the AC drive controls the speed of the
variable speed drive and gives control signals to start and stop the auxiliary drives to control
the total flow. In addition to the eight parameter groups provided as standard, a parameter
group for multi-pump and fan control functions is available.
The application has two control places on the I/O terminal. Place A is the pump and fan
control and place B is the direct frequency reference. The control place is selected with input
DIN6.
As already its name tells, the Pump and Fan Control Application is used to control the
operation of pumps and fans. It can be used, for example, to decrease the delivery pressure
in booster stations if the measured input pressure falls below a limit specified by the user.
The application utilizes external contactors for switching between the motors connected to
the AC drive. The autochange feature provides the capability of changing the starting order of
the auxiliary drives. Autochange between 2 drives (main drive + 1 auxiliary drive) is set as
default, see Chapter 8.11 Automatic changing between drives (application 7 only).
All inputs and outputs are freely programmable.
Additional functions:
Analogue input signal range selection
Two frequency limit supervisions
Torque limit supervision
Reference limit supervision
Second ramps and S-shape ramp programming
Programmable Start/Stop and Reverse logic
DC-brake at start and stop
Three prohibit frequency areas
Programmable U/f curve and switching frequency
Autorestart
Motor thermal and stall protection: fully programmable; off, warning, fault
Motor underload protection
Input and output phase supervision
Sleep function
The parameters of the Pump and Fan Control Application are explained in Chapter 8
Parameter descriptions of this manual. The explanations are arranged according to the
individual ID number of the parameter.
VACON · 196 PUMP AND FAN CONTROL APPLICATION
7
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled