2 STANDARD APPLICATION
2.1 INTRODUCTION
Select the Standard Application in menu M6 on page S6.2.
The Standard Application is typically used in pump and fan applications and conveyors for
which the Basic Application is too limited but where no special features are needed.
The Standard Application has the same I/O signals and the same control logic as the
Basic Application.
Digital input DIN3 and all the outputs are freely programmable.
Additional functions:
Programmable Start/Stop and Reverse signal logic
Reference scaling
One frequency limit supervision
Second ramps and S-shape ramp programming
Programmable start and stop functions
DC-brake at stop
One prohibit frequency area
Programmable U/f curve and switching frequency
Autorestart
Motor thermal and stall protection: Programmable action; off, warning, fault
The parameters of the Standard Application are explained in Chapter 8 Parameter
descriptions of this manual. The explanations are arranged according to the individual ID
number of the parameter.
STANDARD APPLICATION VACON · 19