EasyManuals Logo

Vacon NX series Applications Manual

Vacon NX series
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #222 background imageLoading...
Page #222 background image
7.4.5 DRIVE CONTROL PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.4
Table 97: Drive control parameters, G2.4
Index Parameter Min Max Unit Default Cust ID Description
P2.4.1 Ramp 1 shape 0.0 10.0 s 0.1 500
Smooth ratio for S-
curves.
0 = Linear
100 = full acc/dec
inc/dec tmes
P2.4.2 Ramp 2 shape 0.0 10.0 s 0.0 501
Smooth ratio for S-
curves.
0 = Linear
100 = full acc/dec
inc/dec tmes
P2.4.3
Acceleration time
2
0.1 3000.0 s 1.0 502
P2.4.4
Deceleration time
2
0.1 3000.0 s 1.0 503
P2.4.5 Brake chopper 0 4 0 504
0 = Disabled
1 = Used when
running
2 = External brake
chopper
3 = Used when
stopped/running
4 = used when
running (no test-
ing)
P2.4.6 Start function 0 2 0 505
0 = Ramp
1 = Flying start
2 = Conditional fly-
ing start
P2.4.7 Stop function 0 3 0 506
0 = Coasting
1 = Ramp
2 = Ramp+Run
enable coast
3 = Coast+Run
enable ramp
P2.4.8
DC braking cur-
rent
0.00 I
L
A 0.7 x I
H
507
VACON · 222 PUMP AND FAN CONTROL APPLICATION
7
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled

Related product manuals