Table 96: Analogue output 3 (Control keypad: Menu M2 -> G2.3.7)
Index Parameter Min Max Unit Default Cust ID Description
P2.3.5.1 *
Analogue output 3
signal selection
0.1 E.10 0.1 478
TTF programming
method used. See
Chapter 8.9 "Ter-
minal to function"
(TTF) programming
principle.
P2.3.5.2
Analogue output 3
function
0 4 4 479
See P2.3.5.2
P2.3.5.3
Analogue output 3
filter time
0.00 10.00 s 1.00 480
0 = No filtering
P2.3.5.4
Analogue output 3
inversion
0 1 0 481
0 = Not inverted
1 = Inverted
P2.3.5.5
Analogue output 2
minimum
0 1 0 482
0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.5.6
Analogue output 3
scale
10 1000 % 100 483
P2.3.5.7
Analogue output 3
offset
-100.00 100.00 % 0.00 484
* = Use TTF method to program these parameters.
PUMP AND FAN CONTROL APPLICATION VACON · 221