2.2 CONTROL I/O
1
6
2
3
4
5
18
19
20
12
7
13
8
9
10
14
15
16
21
22
23
11
17
24
25
26
DIN4
DIN5
mA
READY
RUN
AO1-
DO1
+24 V
GND
GND
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
R O1
R O1
R O1
CMA
CMB
R O2
R O2
R O2
OPTA1
OPTA2
Terminal Signal Description
+10 V
ref
AI1+
AI1-
AI2+
AI2-
+24V
Reference output
I/O Ground
Analogue input 2
Current range
0—20mA
Control voltage output
I/O ground
Start forward
Programmable logic (P2.2.1)
Start reverse
Ri min = 5
External fault input
Programmable (P2.2.2)
Preset speed select 1
Preset speed select 2
Fault reset
Common for DIN 1—DIN 3
Common for DIN4—DIN6
Control voltage output
I/O ground
Analogue output 1
Output frequency
Programmable (P2.3.2)
Digital output 1
READY
Programmable (P2.3.7)
Open collector,
I50 mA, U48 VDC
Relay output 1
RUN
Programmable
(P2.3.8)
Relay output 2
FAULT
Programmable
(P2.3.9)
Range 0—20 mA/R
L
,
max. 500 Ω
Connect to GND or +24 V
Contact open = no action
Contact closed = fault reset
AO1+
Analogue input 1
frequency reference
Ground for reference
and controls
Analogue input 2
frequency reference
Contact closed = start forward
Contact closed = start reverse
Contact open = no fault
Contact closed = fault
Freq. ref.
Open
Closed
Open
Closed
Open
Open
Closed
Closed
I/O Reference
Preset Speed 1
Preset Speed 2
Analog input 2
Voltage for potentiometer, etc.
Analogue input 1
Voltage range 0—10V DC
Programmable (P2.1.11)
Voltage for switches,
etc. max 0.1 A
Voltage for switches (see #6)
Connect to GND or +24 V
Ground for reference and controls
Ground for reference and controls
Reference potentiometer,
1-10kΩ
Fig. 4: Standard application default I/O configuration
VACON · 20 STANDARD APPLICATION
2
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents