2.4.9 AUTORESTART PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.8)
Table 12: Autorestart parameters, G2.8
Index Parameter Min Max Unit Default Cust ID Description
P2.8.1 Wait time 0.10 10.00 s 0.50 717
The wait time
before the first
reset is done.
P2.8.2 Trial time 0.00 60.00 s 30.00 718
When the trial time
is over, and the
fault is still active,
the drive will trip.
P2.8.3 Start function 0 2 0 719
The selection of
the start mode for
Automatic reset.
0 = Ramp
1 = Flying start
2 = According to
P2.4.6
P2.8.4
Number of tries
after undervoltage
trip
0 10 0 720
P2.8.5
Number of tries
after overvoltage
trip
0 10 0 721
P2.8.6
Number of tries
after overcurrent
trip
0 3 0 722
P2.8.7
Number of tries
after 4mA refer-
ence trip
0 10 0 723
P2.8.8
Number of tries
after motor tem-
perature fault trip
0 10 0 726
P2.8.9
Number of tries
after external
fault trip
0 10 0 725
P2.8.10
Number of tries
after underload
fault trip
0 10 0 738