300 START/STOP LOGIC SELECTION 2346 (2.2.1, 2.2.1.1)
Table 115: Selections for parameter ID300
Selection DIN1 DIN2 DIN3
0
closed contact = start forward closed contact = start reverse
See Fig. 30.
1
closed contact = startopen
contact = stop
closed contact = reverseopen
contact = forward
See Fig. 31.
2
closed contact = startopen
contact = stop
closed contact = start enable-
dopen contact = start disabled
and drive stopped if running
can be programmed for reverse
command
3 *
closed contact= start pulse open contact = stop pulse can be programmed for reverse
command
See Fig. 32.
Applications 2 and 4:
4
closed contact = start forward
(Rising edge required to start)
closed contact = start reverse
(Rising edge required to start)
5
closed contact = start (Rising
edge required to start)
open contact = stop
closed contact = reverse
open contact = forward
6
closed contact = start (Rising
edge required to start)
open contact = stop
closed contact = start enabled
open contact = start disabled
and drive stopped if running
can be programmed for reverse
command unless selected for
DIN2
Applications 3 and 6:
4
closed contact = start forward closed contact = reference
increases (motor potentiome-
ter reference; this parameter
is automatically set to 4 if
parameter ID117 is set to 4
[Application 4]).
5
closed contact = start forward
(Rising edge required to start)
closed contact = start reverse
(Rising edge required to start)
6
closed contact = start (Rising
edge required to start)
open contact = stop
closed contact = reverse
open contact = forward
VACON · 250 PARAMETER DESCRIPTIONS