323 AI1 SIGNAL INVERSION 3457 (2.2.7, 2.2.19, 2.2.2.6)
If this parameter = 0, no inversion of analogue input signal takes place
NOTE!
In application 3, AI1 is place B frequency reference if parameter ID131= 0 (default).
100%0
ID304
ID303
ID321 ID322
ID320 = 0
AI1 = 0—100%
f
out
AI1
(term. 2)
ID320 = 1
AI1 = custom
Fig. 42: AI1 no signal inversion
If this parameter = 1 inversion of analogue input signal takes place.
Max. AI1 signal = minimum frequency ref.
Min. AI1 signal = maximum frequency ref.
100%0
ID304
ID303
ID321 ID322
ID320 = 0
AI1 = 0—100%
f
out
AI1
(term. 2)
ID320 = 1
AI1 = custom
Fig. 43: AI1 signal inversion
324 AI1 SIGNAL FILTER TIME 34567 (2.2.8, 2.2.20, 2.2.2.2)
This parameter filters out disturbances in the analogue input signal. To activate this
parameter, give it a value that is bigger than 0.
VACON · 266 PARAMETER DESCRIPTIONS