374 ANALOGUE INPUT SUPERVISED VALUE 7 (2.3.2.15)
The value of the selected analogue input to be supervised by parameter ID373.
375 ANALOGUE OUTPUT OFFSET 67 (2.3.5.7, 2.3.3.7)
Add –100.0 to 100.0% to the analogue output signal.
376 PID SUM POINT REFERENCE (PLACE A DIRECT REFERENCE) 5 (2.2.4)
Defines which reference source is added to PID controller output if PID controller is used.
Table 146: Selections for parameter ID376
Selection
number
Selection name Description
0 No additional reference (Direct PID output value)
1
PID output + AI1 reference from
terminals 2 and 3 (e.g. potenti-
ometer)
2
PID output + AI2 reference from
terminals 4 and 5 (e.g. trans-
ducer)
3
PID output + PID keypad refer-
ence
4
PID output + Fieldbus reference
(FBSpeedReference)
5
PID output + Motor potentiome-
ter reference
6
PID output + Fieldbus + PID
output (ProcessDataIN3)
see Chapter 8.7 Fieldbus control parameters (IDs 850 to 859)
7
PID output + Motor potentiome-
ter
If value 7 is selected for this parameter, the values of parameters ID319 and ID301 are
automatically set to 13.
PARAMETER DESCRIPTIONS VACON · 285