NOTE: The UPS meets the standard requirement of short time withstand current (Icw) of 10 kA. The specified
upstream fuses are required to obtain the conditional short circuit current rating, Icc at 65 kA symmetrical rms. It is
recommended to select the fuses in compliance with voltage of 690 V, current of 1500 A and breaking of 200 kA. The
specified upstream breakers should comply with an IEC 60269 series standard.
Product Model
120 kVA APM 0120kMK16FY02S00
Table 1.1 UPS Models
There are 3 types of cabinets for 120 kVA products.
1. UPS without switch.
2. UPS with maintenance switch Q3 cabinet.
3. UPS with input switch Q1, bypass switch Q2, maintenance switch Q3, output switch Q5 cabinet.
Hereinafter referred to as no switch, single switch, and four switches.