7.18 Battery Maintenance
For the battery maintenance and maintenance precautions, refer to IEEE-Std-1188-2005 and the relevant manuals provided
by the battery manufacturer.
Important maintenance steps to be followed:
1. Periodically check and tighten screws at the battery connection points.
2. Ensure that all safety devices are operating normally.
3. Make sure that all battery management parameters are set properly.
4. Measure and record the air temperature inside the battery room.
5. Make sure that the battery terminals have no damage or heat generating trace.
6. Ensure the battery enclosure and terminal shields are intact.
7.19 Disposal of Used Battery
If the battery has liquid leakage or is damaged, place the battery into the container that can withstand sulphuric acid and
discard it according to the local regulations.
Used lead acid storage battery belongs to dangerous. The storage, transportation, use and disposal of the battery must
comply with the national and local laws and regulations on dangerous waste and used battery pollution prevention and other
standards.
According to the relevant national regulations, the used lead acid storage battery must be recycled and must not be disposed
using other methods. Random discard or any other improper disposal of the used lead acid storage battery may cause severe
environment pollution and the relevant person will be investigated of corresponding legal responsibilities.