EasyManua.ls Logo

Vertiv Liebert APM2 - Specifications; Conformance and Standards; Environmental Characteristics

Vertiv Liebert APM2
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12 Specifications
This chapter includes all the required UPS specifications.
12.1 Conformance and Standards
The UPS is designed to comply with the European and international standards listed in Table 12.1 below.
Item Normative Reference
General safety requirements for UPS EN62040-1/IEC62040-1/AS62040-1
EMC requirements for UPS EN62040-2/IEC62040-2/AS62040-2 (Class C3)
Method of specifying the performance and test requirements of UPS EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111)
SPD requirements YD/T1095 (8/20 μs 5 kA)
Table 12.1 European and International Standards
NOTE: The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards
for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction
(IEC/EN/AS60146 series and 60529).
12.2 Environmental Characteristics
Item Unit
Rated Power (kVA)
120
Noise within 1 m (in the front) dB (A) 65
Altitude m 1500; derate power by 1% per 100 m between 1500 m and 3000 m
Relative humidity %RH 0 to 95%, non-condensing
Operating temperature °C
0 to 50,
0 to 40 at full load,
41 to 45 at 90% load,
46 to 50 at 80% load
Storage and transportation temperature for UPS °C Storage: -40 °C to +70 °C; transportation: -40 °C to +70 °C
Over voltage level Level 2
Pollution level Level 2
Grid system TN, TT, IT
Table 12.2 Environmental Characteristics
12 Specifications Proprietary and Confidential ©2023 Vertiv Group Corp. 171
Vertiv™ Liebert® APM2 30 to 120 kVA Modular UPS User Manual

Table of Contents

Other manuals for Vertiv Liebert APM2

Related product manuals