1. If Auto Recovery after EOD Enabling is enabled.
2. After the Auto Recovery after EOD Delay Time expires (the default delay is 10 minutes), the UPS restarts bypass,
then inverter. During the automatic recovery delay, the UPS will charge its batteries to provide a safety margin for
equipment shutdown if input power fails again.
NOTE: During the automatic restart process, manual startup is disabled. Automatic restart must be set by Vertiv's
authorized service engineer through Vertiv setting software.