Figure 5.17 Inverter On Screen
Inverter off
The Inverter Off menu item is available whenever the UPS has input power and the inverter is Off. Before executing the
command, verify that the UPS and connected load are prepared for the inverter to be shutdown. Click Off to turn the inverter
Off.
CAUTION: Risk of improper operation. Can cause load drop resulting in equipment damage. The Inverter Off
will shut off power to the connected load unless bypass power is available. Before executing this command,
verify that the connected load is either shut off or that input power to the load will be supplied by another
source, such as bypass.
70 Proprietary and Confidential ©2023 Vertiv Group Corp.
5 Operator Control and Display
Panel
Vertiv™ Liebert® APM2 30 to 120 kVA Modular UPS User Manual