EasyManua.ls Logo

Vertiv Liebert STS2/PDU - Page 89

Vertiv Liebert STS2/PDU
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vertiv | Liebert
®
STS2
100-1000A, 50/60Hz User Manual | Rev. 12 | 11/2017 81
Examples of Event Mask Settings
To latch event #001, S1 SCR SHORT, use SPT 4 1 +L.
To disable event #128, CONFIG MODIFIED, from sounding the horn, use SPT 4 100 -A.
To enable event #012, OUT VOLT SENSE FAIL, to Dial and go into the Event Log, use
SPT 4 12 +D+E.
To disable all masks for event #120, INPUT CONTACT #1, use SPT 4 120 -D-L-S-E-A.
To breakdown this syntax for the last example:
•SPT SVT command
4 — group parameter, identifying System Setting group under which the Event Mask settings reside.
120 — item parameter. In this command, that is the event ID.
-D-L-S-E-A — value parameter. In this case, the minus sign (-)disables all masks for the INPUT CONTACT #1 event.

Table of Contents

Related product manuals