Vertiv™ NetSure™ Control Unit (NCU) User Manual
3. Change the following parameters as desired and click on “Set”.
• Voltage Input: Enables or Disables the voltage input for that SMDUE input block. If enabled, go to Advanced Settings
menu / Analogs tab to set the voltage input parameters.
• Fuse Alarm Input: Enables or Disables the fuse alarm input for that SMDUE input block. If enabled, go to Advanced
Settings menu / Fuses tab to set the fuse alarm input parameters.
• Analog Input: Sets the analog input signal to be measured for that SMDUE input block. Choices are disable this input
or measure a current transducer (0 mA to 20 mA), a voltage transducer (0 V to 10 V), or a temperature probe. Go to
Advanced Settings menu / Analogs tab to set voltage or current transducer input parameters. Go to Settings menu /
Temp Probes tab to set temperature probe parameters.