EasyManuals Logo

Vertiv NetSure M830B User Manual

Vertiv NetSure M830B
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #256 background imageLoading...
Page #256 background image
Vertiv™ NetSure™ Control Unit (NCU) User Manual
246
<dirn>
This is the direction of the alarm condition. This parameter does not apply to this application. A <null> value is the only
value which is accepted for this parameter. If any other value is received for this parameter, an error response is
returned with the error code INUP.
<tmper>
This is the accumulation time period for PM parameters. This parameter does not apply to this application. A <null>
value is the only value which is accepted for this parameter. Other values for this parameter generate an error response
using the error code “INUP”.
Normal Response Format:
No response is returned if a valid User session has not been established. Otherwise the response is in the following format.
cr lf lf
^^^<source identifier>^<date>^<time> cr lf
M^^<ctag>^COMPLD [ <rspblk>] cr lf ;
<rspblk>
This is the response block which may be repeated multiple times.
cr lf
^^^”[<aid>][,<aidtype>]:<ntfcncde>,<condtype>,<srveff>, [<ocrdat>],[<ocrtm>],[<locn>],[<dirn>][,<tmper>]
[:[<conddescr>],[<aiddet>][,<obsdbhvr>[,<exptdbhvr>]] [:[<dgntype>][,<tblistl>]]]”
<aidtype>
This is the type of access identifier. Valid values for this application are:
EQPT equipment
If the command code modifier is ALL, <aidtype> is required to specify the type of access identifier, else <aidtype> may
be <null>.
<ntfcncde>
This is the notification code associated with a single alarm condition given in this block.
<condtype>
This is the condition type of the alarm condition being given in this block.
<srveff>
This is the effect on service caused by the single alarm condition given in this block.
<ocrdat>
This is the date when the triggering event occurred. The format for this parameter is MOY-DOM(Month-Of-Year - Day-
Of-Month). MOY ranges from 1 to 12 and DOM ranges from 1 to 31.
A <null> value for this parameter defaults to the current date unless <ocrtm> is <null>, then this parameter does not
apply.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure M830B and is the answer not in the manual?

Vertiv NetSure M830B Specifications

General IconGeneral
BrandVertiv
ModelNetSure M830B
CategoryController
LanguageEnglish

Related product manuals