Vertiv™ NetSure™ Control Unit (NCU) User Manual
74
Table 2.3
Alarm Name Alarm Description Action to Correct
SMTemp1 Temp1 High 2
Temperature sensor #1 (connected to SM-Temp 1 and
set as Battery) sensing temperature higher than high
temperature threshold 2.
Check why temperature is high or low. SMTemp1 Temp1 High 1
Temperature sensor #1 (connected to SM-Temp 1 and
set as Battery) sensing temperature higher than high
temperature threshold 1.
SMTemp1 Temp1 Low
Temperature sensor #1 (connected to SM-Temp 1 and
set as Battery) sensing temperature lower than low
temperature threshold.
SMTemp1 Temp8 High 2
Temperature sensor #8 (connected to SM-Temp 1 and
set as Battery) sensing temperature higher than high
temperature threshold 2.
Check why temperature is high or low. SMTemp1 Temp8 High 1
Temperature sensor #8 (connected to SM-Temp 1 and
set as Battery) sensing temperature higher than high
temperature threshold 1.
SMTemp1 Temp8 Low
Temperature sensor #8 (connected to SM-Temp 1 and
set as Battery) sensing temperature lower than low
temperature threshold.
SMTemp8 Temp1 High 2
Temperature sensor #1 (connected to SM-Temp 8 and
set as Battery) sensing temperature higher than high
temperature threshold 2.
Check why temperature is high or low. SMTemp8 Temp1 High 1
Temperature sensor #1 (connected to SM-Temp 8 and
set as Battery) sensing temperature higher than high
temperature threshold 1.
SMTemp8 Temp1 Low
Temperature sensor #1 (connected to SM-Temp 8 and
set as Battery) sensing temperature lower than low
temperature threshold.
SMTemp8 Temp8 High 2
Temperature sensor #8 (connected to SM-Temp 8 and
set as Battery) sensing temperature higher than high
temperature threshold 2.
Check why temperature is high or low. SMTemp8 Temp8 High 1
Temperature sensor #8 (connected to SM-Temp 8 and
set as Battery) sensing temperature higher than high
temperature threshold 1.
SMTemp8 Temp8 Low
Temperature sensor #8 (connected to SM-Temp 8 and
set as Battery) sensing temperature lower than low
temperature threshold.
BTRM Temp High 2
Battery temperature (monitored by the sensor set as
BTRM) is higher than the BTRM Temperature Alarm 2
threshold.
Check why temperature is high or low.
BTRM Temp High 1
Battery temperature (monitored by the sensor set as
BTRM) is higher than the BTRM Temperature Alarm 1
threshold.
BTRM Sensor Fail BTRM temperature sensor failure. Replace temperature sensor.
Inventory Update In Process
Only available if NCU configuration includes the Li-Ion
battery interface.
Li-Ion Battery inventory being updated.
--
ABCL is active
Only available if NCU configuration includes the Li-Ion
battery interface.
Active Battery Charge Current Limit is active.
--
Battery Charge Prohibited Alarm
Only available if NCU configuration includes the Li-Ion
battery interface.
A battery charge prohibited alarm is active.
See why alarm is active.