EasyManuals Logo

Vertiv NetSure M830B User Manual

Vertiv NetSure M830B
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #84 background imageLoading...
Page #84 background image
Vertivâ„¢ NetSureâ„¢ Control Unit (NCU) User Manual
74
Table 2.3
Alarm Name Alarm Description Action to Correct
SMTemp1 Temp1 High 2
Temperature sensor #1 (connected to SM-Temp 1 and
set as Battery) sensing temperature higher than high
temperature threshold 2.
Check why temperature is high or low. SMTemp1 Temp1 High 1
Temperature sensor #1 (connected to SM-Temp 1 and
set as Battery) sensing temperature higher than high
temperature threshold 1.
SMTemp1 Temp1 Low
Temperature sensor #1 (connected to SM-Temp 1 and
set as Battery) sensing temperature lower than low
temperature threshold.
… … …
SMTemp1 Temp8 High 2
Temperature sensor #8 (connected to SM-Temp 1 and
set as Battery) sensing temperature higher than high
temperature threshold 2.
Check why temperature is high or low. SMTemp1 Temp8 High 1
Temperature sensor #8 (connected to SM-Temp 1 and
set as Battery) sensing temperature higher than high
temperature threshold 1.
SMTemp1 Temp8 Low
Temperature sensor #8 (connected to SM-Temp 1 and
set as Battery) sensing temperature lower than low
temperature threshold.
… … …
SMTemp8 Temp1 High 2
Temperature sensor #1 (connected to SM-Temp 8 and
set as Battery) sensing temperature higher than high
temperature threshold 2.
Check why temperature is high or low. SMTemp8 Temp1 High 1
Temperature sensor #1 (connected to SM-Temp 8 and
set as Battery) sensing temperature higher than high
temperature threshold 1.
SMTemp8 Temp1 Low
Temperature sensor #1 (connected to SM-Temp 8 and
set as Battery) sensing temperature lower than low
temperature threshold.
… … …
SMTemp8 Temp8 High 2
Temperature sensor #8 (connected to SM-Temp 8 and
set as Battery) sensing temperature higher than high
temperature threshold 2.
Check why temperature is high or low. SMTemp8 Temp8 High 1
Temperature sensor #8 (connected to SM-Temp 8 and
set as Battery) sensing temperature higher than high
temperature threshold 1.
SMTemp8 Temp8 Low
Temperature sensor #8 (connected to SM-Temp 8 and
set as Battery) sensing temperature lower than low
temperature threshold.
BTRM Temp High 2
Battery temperature (monitored by the sensor set as
BTRM) is higher than the BTRM Temperature Alarm 2
threshold.
Check why temperature is high or low.
BTRM Temp High 1
Battery temperature (monitored by the sensor set as
BTRM) is higher than the BTRM Temperature Alarm 1
threshold.
BTRM Sensor Fail BTRM temperature sensor failure. Replace temperature sensor.
Inventory Update In Process
Only available if NCU configuration includes the Li-Ion
battery interface.
Li-Ion Battery inventory being updated.
--
ABCL is active
Only available if NCU configuration includes the Li-Ion
battery interface.
Active Battery Charge Current Limit is active.
--
Battery Charge Prohibited Alarm
Only available if NCU configuration includes the Li-Ion
battery interface.
A battery charge prohibited alarm is active.
See why alarm is active.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure M830B and is the answer not in the manual?

Vertiv NetSure M830B Specifications

General IconGeneral
BrandVertiv
ModelNetSure M830B
CategoryController
LanguageEnglish

Related product manuals