Vertiv™ NetSure™ Control Unit (NCU) User Manual
83
Table 2.3
Alarm Name Alarm Description Action to Correct
TranCurr10 Low1 Curr Alarm
Monitored Transducer Current10 is lower than the Low1
Curr Alarm threshold.
Check why current is high or low.
TranCurr10 Low2 Curr Alarm
Monitored Transducer Current10 is lower than the
Low2 Curr Alarm threshold.
TranCurr10 High1 Curr Alarm
Monitored Transducer Current10 is higher than the
High1 Curr Alarm threshold.
TranCurr10 High2 Curr Alarm
Monitored Transducer Current10 is higher than the
High2 Curr Alarm threshold.
SMDUEDCFuseUnit 1-8 (SM-DUE Module must be present in system) Alarms
DC Fuse 1 Alarm DC fuse #1 is open.
Find out and eliminate the reason the fuse is open
before replacing. Check for overload or short circuit. If
the fuse was manually removed, check with the person
that removed it before reinserting it.
DC Fuse 10 Alarm DC fuse #10 is open.