Chapter 4 Deployment of the CPU 21x-2BT10 with TCP/IP Manual VIPA CPU 21x
4-48 HB103E - Rev. 05/45
Start NetPro by selecting the CPU below Station 1 and clicking on the
object "connections".
In NetPro "Station 1" and "Station 2" are listed together with Ethernet.
Ethernet
CPU
315-2
DP MPI CP
343-1
Station 1
CPU
315-2
DP MPI CP
343-1
Station 2
To configure the connection open the connection list. For this you choose
the CPU of Station 1 and call Insert new connection via the context menu:
CPU
315-2
DP MPI CP
343-1
Station 1
Insert new connection
A dialog window appears where you can select the connection partner and
the type of the connection.
Configure the following connection:
New connection
Connection: TCP connection
Connection partner: Station 2 > CPU 315-2
Properties TCP connection
ID: 1
ID and LADDR are parameters that you have to define in
your PLC program if using FC5 (AG_SEND) and FC6
(AG_RECEIVE).
Route: The Route allows you to choose the CP that has to
manage the connection.
For the communication between the CPU 21xNET the
route "CP 343-1 - (R0/S4)" is just right preset.
Active connection establishment: activated
Save and compile your connection.
Project engineering
with NetPro